2. Choose System Settings > Signal Name Modify. The Batch Signal
Conguration tab page is displayed.
3. Set Device type to ECC800, set Device name to ECC800, and click OK.
4. On the query result tab page, set the new signal name of AI/DI_1 to Smoke
and click Submit.
5. Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1
Port Settings.
6. Set Smoke sensor to Enable and click Submit.
Step 2 Check the monitoring functions of smoke detector.
Table 5-5 Commissioning the detector
Check Method Normal Connection Status Alarm Clearance Method
Simulate a
smoky
environment
under the smoke
detector.
Smoke DI alarm is displayed
on the active alarm page of
the app or WebUI.
Disconnect the smoke
detector cable and then
reconnect it to clear the
alarm.
----End
5.3.6.2 Commissioning a T/H Sensor
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port
on the T/H sensor, and the other end has been connected to the COM port on the
ECC800-Pro.
Procedure
Step 1 Set a device address for the T/H sensor.
Operate the DIP switch on the T/H sensor to set the device address for the sensor.
Toggle switches 1 to 6 specify the device address in binary mode. ON indicates 1,
and OFF indicates 0.
FusionModule500 Smart Mini Data Center
User Manual 5 Power-On Commissioning
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 126