5.2.1 Powering on Devices
Prerequisites
Check that the
humidier water inlet pipe and drainpipe are correctly
connected, that the thermal insulation foam is intact, and that refrigerant has
been charged.
Check that the smart cooling product circuit breaker in the upstream PDB is
OFF.
Check that the power cable is correctly connected and that the input voltage
meets requirements.
Check that the smart cooling product control unit and the ECC800-Pro are
correctly connected.
Procedure
Step 1 Switch on the smart cooling product circuit breaker in the upstream PDB.
NO TICE
The electric heating belt of the crankcase starts working. Before starting the
compressor, ensure that the electric heating belt of the crankcase has been
preheated for more than 12 hours. Otherwise, maintenance is not performed.
Step 2 Commission the system after the electric heating belt of the crankcase has been
preheated for 12 hours.
----End
5.2.2 Performing Initial Conguration
Prerequisites
One end of the straight-through cable has been connected to the communications
port on the NetCol8000-A0131, and the other end has been connected to the
COM port on the ECC800-Pro.
Procedure
Step 1 Add the NetCol8000-A0131.
1. Log in to the ECC800 WebUI as an administrator.
2. Add the NetCol8000-A0131.
Table 5-1 Adding a smart cooling product
Path
Parameter Setting
Choose
System
Device
Attribute
Select Air Conditioner from the drop-
down list box.
FusionModule500 Smart Mini Data Center
User Manual 5 Power-On Commissioning
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 112

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 V100R021C10 and is the answer not in the manual?

Huawei FusionModule500 V100R021C10 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500 V100R021C10
CategoryData Loggers
LanguageEnglish

Related product manuals