Saturation
Temperatu
re (°C)
Gauge
Pressure
(MPa)
Saturation
Temperatu
re (°C)
Gauge
Pressure
(MPa)
Saturation
Temperatu
re (°C)
Gauge
Pressure
(MPa)
7 0.9 26 1.60 45 2.63
8 0.93 27 1.65 46 2.7
9 0.96 28 1.69 47 2.76
10 0.99 29 1.74 48 2.83
11 1.02 30 1.79 49 2.9
12 1.05 31 1.84 50 2.97
13 1.09 32 1.89 51 3.04
14 1.12 33 1.94 52 3.11
15 1.16 34 1.99 53 3.19
16 1.19 35 2.04 54 3.26
17 1.23 36 2.1 55 3.34
18 1.27 37 2.15 - -
NO TE
1 MPa ≈ 10 bar ≈ 145 psi ≈ 10.2 kgf/cm
2
NO TICE
Users include admin (preset password: Changeme) and operator (preset
password: Changeme). To enter the diagnostic mode, log in as user admin.
If a smart cooling product is not
congured with a heater or humidier, skip
the commissioning steps related to the electric heater and wet lm humidier.
Procedure
Step 1 Log in to the ECC800 WebUI as user admin. Choose Monitoring > Cooling >
NetCol8000-A0131. The page for commissioning smart cooling products is
displayed.
NO TE
If no manual operation is performed within 25 seconds after you click On, the device will
automatically run following the preset logic, and the compressor and indoor and outdoor
fans will also run according to the environment.
Step 2 Choose Controls > Control Information, set Power on/o to ON, and click
Submit.
FusionModule500 Smart Mini Data Center
User Manual 5 Power-On Commissioning
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 115