iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Copyright © Huawei Technologies Co., Ltd.
247
Figure 6-85 Page for setting management attributes
IP Address indicates the ECC800 login IP address. Port indicates the ECC800 COM2 port (3212).
Device Address indicates the Polymer T/H sensor address.
Step 12 Click to save the created device view.
Step 13 Choose Configuration > Transmission Channel Management > Energy Controller
Transparent Channel Settings.
Step 14 Click Modify after selecting the IP address of the ECC800 connected to the NMS.