iManager NetEco 6000
Device Installation and Commissioning Guide
3 Installing Devices
Copyright © Huawei Technologies Co., Ltd.
31
Figure 3-24 Installing a cable nail clip
When laying out the water detection cable, ensure that the water detector is close to the
planned position for the network cabinet to facilitate further cable connections.
The water detection cable should not be laid out near air exhaust vents of smart cooling
products. If unavoidable, take measures to prevent condensation.
Step 5 Place the water detection cable onto the fastener, secure the fastener, and keep the water
detection cable in close contact with the floor.
Figure 3-25 Securing a water detection cable
If multiple water detection cables need to be connected in series, connect the male connector of one
cable to the female connector of another cable.
----End