(10) AC output (11) Reserved port (12) DIP switch
(13) FE ports (14) COM and dry contact
ports
(15) WiFi switch
(16) Manual ON/OFF switch
DIP Switch
Figure 4-3 DIP switch
Table 4-1 DIP switch description
Parallel
Power
Module
CAN
Address
Pin 1
(M/S)
Pin 2 (A) Pin 3 (B) Pin 4 (C) Remarks
1 ON OFF OFF OFF Master
address
2 OFF ON OFF OFF Slave
address
3 OFF OFF ON OFF Slave
address
NOTE
● Pin 1 (M/S) indicates whether the product is a master or slave. When Pin 1 is set to ON,
the product is a master product. Otherwise, the product is a slave product. Pins 2–4 (A–
C) indicate the high-speed CAN communication addresses in a parallel system.
● When only one product is used, set Pin 1 to ON.
● The default address is 0 (Pin 1 to Pin 4: OFF).
COM and Dry Contacts
Figure 4-4 Wiring terminals
iSitePower-M (MAP05A1, MAB05B1)
User Manual 4 Components
Issue 02 (2021-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 23