NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
5 Power-On Commissioning
Copyright © Huawei Technologies Co., Ltd.
149
Check Item
Actual Result
All circuit breakers are on.
□Passed. □Failed.
The drainage button on the electrical control box is in the position
of normal humidifying.
□Passed. □Failed.
No oil stain exists on the copper pipe thermal insulation foam or
bottom plate, or it has been cleaned.
□Passed. □Failed.
5.7 Power Off
Procedure
Step 1 On the home page, tap Shutdown.
Exercise caution during operation because the unit is still live.
Step 2 Switch off the general circuit breaker QF1.
Step 3 If the smart cooling product needs to be maintained in power-off mode or long-term
power-off, switch off the smart cooling product external circuit breaker.
----End