6.2.4 Monthly Maintenance
Table 6-3 lists monthly maintenance items for the indoor unit. If parts replacement is required,
contact Huawei technical support to obtain spare parts.
Table 6-3 Monthly maintenance checklist
The air filter surface is free of
accumulated dust, damage, and
deformation.
Replace the air filter. Huawei
recommends replacing the air filter once
every six months. See 6.5.1 Replacing
Filters for the replacement method.
The compressor generates no
abnormal noises, such as metal
friction noise.
Slightly shake the compressor and touch
the four anchor bolt to check whether
they are loose. If they are loose, tighten
them using a 13# solid wrench. If the
problem persists, contact Huawei
technical support.
Run the indoor unit and check that
the oil level is stably above 1/3 of
the oil sight glass and that no
dense white bubbles cover the
entire glass surface.
Add refrigerant oil. For details, contact
Huawei technical support.
The humidifier cylinder interior
wall is free from large quantity of
water scale.
Replace the humidifier cylinder by
referring to 6.5.6 Replacing Humidifier
Cylinder. Huawei recommends replacing
the humidifier cylinder once every six
months.