Chapter 3 Operation
POWER CON
PCON-CB/LC
147
[9] Alarm, Alarm Reset (*ALM, RES)
Input Output
PIO signal
RES *ALM
1) Alarm signal *ALM is set to ON in the normal status but turned OFF at the occurrence of an
alarm at a level equal to or higher than the operation release level.
2) Turning reset signal RES ON under occurrence of an alarm at the operation release level
allows the alarm
(Note 1)
to be released. The action is taken at the rising edge (ON edge).
3) The alarm reset should be done after the cause of the alarm is confirmed and removed. If
alarm reset and restart are repeated many times without removal of the cause, a severe
failure such as motor burnout may occur.
Note 1 Check the 9.4 Alarm List for details of alarms.
Caution: An alarm of the cold start level cannot be cancelled by RES. Confirm the
cause, remove it, and then reboot the unit.
[10] Binary Output of Alarm Data Output (*ALM, ALM1 to 8)
Output
PIO signal
*ALM ALM1 to ALM8
1) If an alarm at a level equal to or higher than the operation release level occurs, alarm
output signals ALM 1 to 8 output the alarm information in the binary code format.
2) The PLC can read the binary code of alarm signal *ALM as the strobe signal to check the
alarm information.
{: ON z: OFF
*ALM ALM8 ALM4 ALM2 ALM1
Binary Code
Description: Alarm code is shown in ( ).
{ z z z z Normal
z z z z { 1 Collision detection (0DF)
z z z { z 2
Software reset during servo ON (090)
Position No. error in teaching (091)
PWRT signal detection during movement (092)
PWRT signal detection in incomplete home return (093)
DCLR signal detection with datum position movement
command (095)
z z z { { 3
Move command during servo OFF (080)
Position command in incomplete home return (082)
Absolute position move command when home return is
not yet completed (083)
Movement Command during Home Return Operation
(084)
Position No. error during movement (085)
Move command while pulse train input is effective (086)
Position command information data error (0A3)
Command deceleration error (0A7)
z z { z z 4
FAN error detection (0D6)
Field bus module not detected (0F3)
Mismatched PCB (0F4)
z z { z { 5
Field bus link error (0F1)
Field bus module error (0F2)
z z { { z 6
Parameter data error (0A1)
Position data error (0A2)
Unsupported motor/encoder type (0A8)
z z { { {
7
Excitement detection error (0B8)
Home sensor non-detection (0BA)
Home return timeout (0BE)
(Note) *ALM Signal is an active low signal. It is ON when the power is applied to the controller, and
turns OFF when the signal is output.

Table of Contents

Other manuals for IAI PCON-CA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IAI PCON-CA Series and is the answer not in the manual?

IAI PCON-CA Series Specifications

General IconGeneral
BrandIAI
ModelPCON-CA Series
CategoryController
LanguageEnglish

Related product manuals