RCON-PS2 Power Supply Connector Wiring When Using Noise Filter
It is not necessary to apply a noise filter on RCON-PS2. However, a noise filter is
required to be applied when the equipment needs to be complied with the CE marking.
Shown below is an example of wiring when a noise filter is to be used.
The leakage current may vary depending on the connected motor capacity,
cable length and other ambient environment. In case of leakage protection,
measure the leakage current at the position to install a leakage breaker.
A leakage breaker should be selected under a clear purpose such as protection
from fire or protection for personnel. Select a leakage breaker applicable for
higher harmonics (inverter).
Example of Wiring for 3-Phase 200V Power Supply
(1)
Example of Wiring for single-Phase 200V Power Supply
(2)
Grounding
Class D Grounding
(former Class 3 Grounding with
ground resistance 100Ω or below)
Surge Protector
RAV-781BXZ-4
(manufactured by
Okaya Electric Industrie)
Leakage Breaker
RCON-PS2-3
Connector Model Code:
SPC 5_4-STF-7,62
I
>
I
>
I
>
Circuit Breaker
L1 L2 L3
Surge Protector
RAV-781BWZ-2A
(manufactured by
Okaya Electric Industrie)
Leakage Breaker
RCON-PS2-3
Connector Model Code:
SPC 5_4-STF-7,62
I
>
I
>
Circuit Breaker
L N
Grounding
Class D Grounding
(former Class 3 Grounding with
ground resistance 100Ω or below)
Noise Filter
TAC-20-683
(manufactured by Cosel)
Noise Filter
NBH-20-432
(manufactured by Cosel)