80070301-0303ffff Sensor [SensorElementName] has transitioned to non-recoverable from a less severe state.
Explanation: IMM has detected that the temperature for CPU 3 has transitioned to a non recoverable state.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0524
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the microprocessor 3 heat sink is securely installed.
5. (Trained service technician only) Make sure that the microprocessor 3 heat sink is installed correctly and the
thermal material is correctly applied.
6. (Trained service technician only) Replace microprocessor 3.
80070301-0304ffff Sensor [SensorElementName] has transitioned to non-recoverable from a less severe state.
Explanation: IMM has detected that the temperature for CPU 4 has transitioned to a non recoverable state.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0524
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the microprocessor 4 heat sink is securely installed.
5. (Trained service technician only) Make sure that the microprocessor 4 heat sink is installed correctly and the
thermal material is correctly applied.
6. (Trained service technician only) Replace microprocessor 4.
80070301-0303ffff 80070301-0304ffff
424
System x3750 M4 Types 8722 and 8733: Installation and Service Guide