Advisor Advanced ATSx000A(-IP) Installation and Programming Manual  141 
8.1.3.6 Installer in-time 
 
6 Inst in-time 
 >00:01’00< 
The Installer in-time menu allows you to configure the time in which an engineer 
is allowed to access when granted by a user (see “8.2.1 User code required” on 
page 143). This time starts when the user activates the option “Installer in”. 
During this time the installer can enter the installer menu and set or unset the 
system. 
When the installer is in the installer menu, this time has no effect on how long the 
installer can stay logged. 
The allowed range is 00 h 01 min to 11 h 59 min. A value of 12 h 00 min is 
equivalent to infinite access. 
8.1.4 Zone timer menu 
 
The Zone timer menu allows you to set up all programmable zone timers. 
8.1.4.1 Double knock interval 
 
If enabled for a particular zone, Double knock interval specifies the maximum 
permitted time between two pulses that will register an alarm. If this value is set 
to 0, an alarm condition is not determined by the interval between two pulses, but 
determined solely by Double knock open time. The allowed range is 0 to 
15 minutes. 
8.1.4.2 Double knock open 
 
If enabled for a particular zone, Double knock open specifies the time for which 
the zone may remain active. If the zone remains active after this time exceeded, 
an alarm is generated without waiting for a second activation. 
The input format is mm’ss. The allowed range is from 00’00 to 15’00. 
8.1.4.3 Soak test 
 
The Soak test option defines the number of days the soak test for a zone is 
active. The allowed range is 0 to 30 days. 
Soak test is activated as soon as the zone option Soak test (see “4.1.n.6.9 Soak 
test” on page 98) for a zone has been set to Yes. During the soak test period the 
zone does not trigger alarms.