Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
potentiomete
r integral
ratio
P08.44
UP/DOWN
terminals
control
0x00~0x221
LED ones: frequency control selection
0:UP/DOWN terminals setting effective
1:UP/DOWN terminals setting ineffective
LED tens: frequency control selection
0:Only effective when P00.06=0 or P00.07=0
1:All frequency means are effective
2:When the multi-step are p
riority, it is ineffective to
the multi-step
LED hundreds: action selection when stop
0:Setting effective
1:Effective in the running, clear after stop
2:
Effective in the running, clear after receiving the
frequency
increasing
integral
DOWN
terminals
frequency
integral ratio
0.01~50.00 Hz/s 0.50 Hz/s
the
frequency
setting is off
0x000~0x111
LED ones: The action selection when the
adjusting the frequency is off.
0:Save when the power is off
1:Clear when the power is off
LED tens:The action selection when MODBUS