Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
above 20% of the rated current, the fan rotates.
1:The fan keeps on running after power on
(generally for the site with high temparature an
PWM
selection
0:PWM mode 1, 3-phase commission and 2-
commission
1:PWM mode 2, 3-phase commission
0
◎
P08.41
Over
commission
selection
0:Invalid
1:Valid
1
◎
P08.42
0x000~0x1223
LED ones:frequency enable selection
0:Both ∧ / ∨
keys and digital potentiometer
adjustments are effective
1:Only ∧/∨ keys adjustments is effective
2:Only digital potentiometer adjustments is effective
keys nor digital potentiometer
adjustments are effective
LED tens: frequency control selection
0:Only effective when P00.06=0 or P00.07=0
1:Effective for all frequency setting manner
2:Ineffective for multi-step speed when multi-step
speed has the priority
LED hundreds: action selection during stopping
0:Setting is valid
1:Valid during running, cleared after stopping
2:
Valid during running, cleared after receiving the
stop command
LED thousands: ∧ / ∨
potentiometer Integral function
0:The Integral function is valid
1:The Integral function is invalid
0x0000