Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
erminal running command channel
(“LOCAL/REMOT” flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi
ommunication running command channel
The running command is controlled by the upper
monitor via communication.
P00.02
This parameter is used to set the maximum output
frequency of the inverter. Users should pay atte
to this parameter because it is the foundation of the
frequency setting and the speed of acceleration and
deceleration.
Setting range: P00.04~400.00Hz
50.00Hz
The upper limit of the running frequency is
limit of the output frequency of the inverter which is
lower than or equal to the maximum frequency.
Setting range:P00.05~P00.03 (
The lower limit of the running freq
output frequency of the inverter.
The inverter runs at the lower limit frequency if the
set frequency is lower than the lower limit one.
Note: Max. output frequency ≥ Upper limit frequency
≥ Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper
running frequency)
0.00Hz