Goodrive200 inverters Function codes
49
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
P00.06
A frequency
command
0
P00.07
B frequency
command
0:Keypad data setting
Modify the value of P00.10 (set the frequency by
keypad) to modify the frequency by the keypad.
1:Analog AI1 setting
2:Analog AI2 setting
3:Analog AI3 setting
Set the frequency by analog input terminals.
Goodrive200 series inverters provide 3 channel
s
analog input terminals as the standard configuration,
of which AI1/AI2 are the voltage/current option
(0~10V/0~20mA) which can be shifted by jumpers;
wh
ile AI3 is voltage input (-10V~+10V).
Note:
when analog AI1/AI2 select 0~20mA input, the
corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds to
the maximum frequency (function code P00.03) in
forward direction and -100.0% c
orresponds to the
maximum frequency in reverse direction (function
code P00.03)
4:High-speed pulse HDI setting
The frequency is set by high-
speed pulse terminals.
Goodrive200 series inverters provide 1 channel
high
speed pulse input as the standard confi
guration. The
pulse frequency range is 0.0~50.00kHz.
100.0% of the high speed pulse input setting
corresponds to the maximum frequency in forward
direction (P00.03) and -
100.0% corresponds to the
maximum frequency in reverse direction (P00.03).
Note: The p
ulse setting can only be input by
multi-
function terminals HDI. Set P05.00 (HDI input
selection) to high speed pulse input, and set P05.49
1