Goodrive200 inverters Function codes
50
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
(HDI high speed pulse input function selection) to
frequency setting input.
5:Simple PLC program setting
The inverte
r runs at simple PLC program mode
when P00.06=5 or P00.07=5. Set P10 (simple PLC
and multi-step
speed control) to select the running
frequency, running direction, ACC/DEC time and the
keeping time of corresponding step
. See the function
description of P10 for detailed information.
6: Multi-step speed running setting
The inverter runs at multi-step
speed mode when
P00.06=6 or P00.07=6. Set P05 to select the current
running step
, and set P10 to select the current
running frequency.
The multi-step speed has
the priority when P00.06 or
P00.07 does not equal to 6, but the setting step
can
only be the 1~15 step. The setting step
is 1~15 if
P00.06 or P00.07 equals to 6.
7: PID control setting
The running mode of the inverter is process PID
control when P00.06=7
or P00.07=7. It is necessary
to set P09. The running frequency of the inverter is
the value after PID effect. See P09 for the detailed
information of the preset source, preset
value,
feedback source of PID.
8:MODBUS communication setting
The frequency is
set by MODBUS communication.
See P14 for detailed information.
9~11: Reserved
Note: A frequency and B frequency can not set as
the same frequency reference mode.