Goodrive200 inverters Function codes
51
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
P00.08
B frequency
command
reference
0:Maximum output frequency, 100% of
B frequency setting corresponds to the maximum
output frequency
1:
A frequency command, 100% of B frequency
setting corresponds to the maximum
output
frequency. Select this setting if it needs to adjust on
the base of A frequency command.
0
P00.09
Combination
of the setting
source
0: A, the current frequency setting is A freauency
command
1: B, the current frequency setting is B frequency
command
2: A+B, the current frequency setting is A frequency
command + B frequency command
3: A-
B, the current frequency setting is A frequency
command - B frequency command
4: Max(A, B):
The bigger one between A frequency
command and B frequency is the set frequency.
5: Min(A, B):
The lower one between A frequency
command and B frequency is the set frequency.
Note:The combination manner can be
shifted by
P05(terminal function)
0
P00.10
Keypad set
frequency
When A and B frequency commands are selected as
“keypad setting”,
this parameter will be the initial
value of inverter reference frequency
Setting range:0.00 Hz~P00.03(the Max. frequency)
50.00Hz
P00.11
ACC time 1
Depend
on model
P00.12
DEC time 1
ACC tim
e means the time needed if the inverter
speeds up from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter
speeds down from the Max. Output frequency to 0Hz
(P00.03).
Goodrive200
series inverters define four groups of
Depend
on model