Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
which can be selected by P05. The
factory default ACC/DEC time of the inverter is the
first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
P00.13
0: Runs at the default direction, the inverter runs in
the forward direction. FWD/REV indicator is off.
1: Runs at the opposite
direction, the inverter runs in
the reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation direction
of the motor. This effect equals
rotation direction by adjusting either two of the motor
lines (U, V and W). In keypad control, t
rotation direction can be changed by QUICK/JOG
the keypad. Refer to parameter P07.02.
Note:
When the function parameter comes back to
the default value, the motor’s running direction will
come back to the factory default state, too. In some
cases it should be used with caut
commissioning if the change of rotation direction is
2: Forbid to run in reverse direction: It can be used in
some special cases if the reverse running is
Carrier
frequency
setting
The relationship table of the
frequency:
Motor type The factory value of
Depend