Goodrive200 inverters Function codes
53
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
carrier frequency
1.5~11kW 8kHz
15~55kW 4kHz
Above 75kW 2kHz
The advantage of high carrier frequency: ideal
current waveform, little current harmonic wave and
motor noise.
The disadv
antage of high carrier frequency:
increasing the switch loss, increasing inverter
temperature and the impact to the output capacity.
The inverter needs to derate on high carrier
frequency. At the same time, the leakage and
electrical magnetic interference will increase.
Applying low carrier frequency is contrary to the
above, too low carrier frequency will cause unstable
running, torque decreasing and surge.
The manufacturer has set a reasonable
carrier
frequency when the inverter is in factory. In genera
l,
users do not need to change the parameter.
When the frequency used exceeds the default carrier
frequency, the inverter needs to derate 20% for each
additional 1k carrier frequency.
Setting range:1.0~15.0kHz
P00.15
Motor
parameter
autotuning
0:No operation
1:Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning
when
high control accuracy is needed.
2:Static autotuning
It is suitable in the cases when t
he motor can not
de-couple form the load. The antotuning
for the
0