Goodrive200 inverters Function codes
68
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
control factor
P04.12
Motor 1
vibration
control
threshold
The setting range of P04.12:0.00Hz~P00.03
(the
Max. frequency)
30.00 Hz
P04.13
P04.14
P04.15
P04.16
P04.17
P04.18
P04.19
P04.20
P04.21
P04.22
P04.23
P04.24
P04.25
P04.26
Energy-savin
g operation
selection
0:No action
1:Automatic energy-saving operation
Motor on the
light load conditions, automatically
adjusts the output voltage to save energy
0
P04.27
Voltage
Setting
Channel
Select the output setting channel
at V/F curve
separation.
0: Keypad setting
voltage: the output voltage is
determined by P04.28.
1:AI1 setting voltage;
2:AI2 setting voltage;
3:AI3 setting voltage;
4:HDI1 setting voltage;
0