Goodrive200 inverters Function codes
69
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
5:Multi-step speed setting voltage;
6:PID setting voltage;
7:MODBUS communication setting voltage;
8~10: Reserved
Note: 100% corresponds to the rated
voltage of the
motor.
P04.28
Keypad
setting
voltage
T
he function code is the voltage digital set value
when the
voltage setting channel is selected as
“keypad selection”
The setting range:0.0%~100.0%
100.0%
P04.29
Voltage
increasing
time
5.0s
P04.30
Voltage
decreasing
time
Voltage increasing time is the time when the
inverter
accelerates from the output minimum voltage to the
output maximum voltage.
Voltage decreasing time is the time when the
inverter
decelerates from the output maximum
voltage to the
output minimum voltage.
The setting range:0.0~3600.0s
5.0s
P04.31
Maximum
output
voltage
100.0%
P04.32
Minimum
output
voltage
Set the upper and low limit of the output voltage.
The setting range of P04.31:P04.32~100.0%(
the
rated voltage of the motor)
The setting range of P04.32:0.0%~ P04.31(the rated
voltage of the motor)
0.0%
P04.33
Reserved