IPE300 series engineering VFD Function parameter list
-242-
Function
code
Name
Description
Default
Modify
P93.10
Lower limit of
PT1000
calibration
temperature
-20.050.0°C
-20.0°C
P93.11
Upper limit of
PT1000
calibration digital
quantity
04096
3800
P93.12
Lower limit of
PT1000
calibration digital
quantity
04096
0
P93.13
PT100/PT1000
disconnection
detection
enabling
0x000x11
Ones place: PT100 disconnection detection
0: Disable
1: Enable
Tens place: PT1000 disconnection detection
0: Disable
1: Enable
0x00
P93.14
PT100 current
temperature
-50.0150.0°C
0.0°C
P93.15
PT100 current
digital volume
04096
0
P93.16
PT1000 current
temperature
-50.0150.0°C
0.0°C
P93.17
PT1000 current
digital volume
04096
0
P93.18
Warning display
04
0: No warning
1: PT100 overtemp (A-Ot1)
2: PT1000 overtemp (A-Ot2)
3: PT100 disconnection (A-Pt1)
4: PT1000 disconnection (A-Pt2)
0
P93.19
Reserved
065535
0
P93.20
Type of sensor
for AI/AO card to
detect motor
temperature
0: No inputs
1: PT100 input
2: PT1000 input
3: KTY84 input
0