IPE300 series engineering VFD Optional peripheral accessories
-353-
D.4.3 Recommended cable size
Table D-1 AC 3PH 380V (-15%)–440V (+10%)
VFD model
Recommended cable size (mm²)
Fixing screw
R, S, T
U, V, W
PE
P1, (+)
PB, (+), (-)
Terminal
screw
Fastening
torque (Nm)
IPE300-01R5-4
1.0/1.0
1.0/1.0
1.0/1.0
1.0/1.0
M4
1.2–1.5
IPE300-02R2-4
1.0/1.5
1.0/1.5
1.0/1.5
1.0/1.5
M4
1.2–1.5
IPE300-0004-4
1.5/2.5
1.5/2.5
1.5/2.5
1.5/2.5
M4
1.2–1.5
IPE300-05R5-4
2.5/4
2.5/4
2.5/4
2.5/4
M5
2–2.5
IPE300-07R5-4
2.5/4
2.5/4
2.5/4
2.5/4
M5
2–2.5
IPE300-0011-4
4/6
4/6
4/6
4/6
M5
2–2.5
IPE300-0015-4
6/10
6/10
6/10
6/10
M5
2–2.5
IPE300-0018-4
10/10
10/10
10/10
10/10
M5
2–2.5
IPE300-0022-4
10/16
10/16
10/16
10/16
M6
4–6
IPE300-0030-4
16/25
16/25
16/25
16/25
M6
4–6
IPE300-0037-4
25/25
16/16
25/25
25/25
M6
4–6
IPE300-0045-4
25/35
16/16
25/35
25/35
M8
9–11
IPE300-0055-4
35/50
16/25
35/50
35/50
M8
9–11
IPE300-0075-4
50/70
25/35
50/70
50/70
M8
9–11
IPE300-0090-4
70/95
35/50
70/95
70/95
M10
18–23
IPE300-0110-4
95/95
50/50
95/95
95/95
M10
18–23
IPE300-0132-4
95/150
50/70
95/150
95/150
M12
31–40
IPE300-0160-4
150/185
70/95
150/185
150/185
M12
31–40
IPE300-0185-4
185/185
95/95
185/185
185/185
M12
31–40
IPE300-0200-4
185/2×95
95/95
185/2×95
185/2×95
M12
31–40
IPE300-0220-4
2×95/2×95
95/95
2×95/2×95
2×95/2×95
M12
31–40
IPE300-0250-4
2×95/2×150
95/150
2×95/2×150
2×95/2×150
M12
31–40
IPE300-0280-4
2×150/2×150
150/150
2×150/2×150
2×150/2×150
M12
31–40
IPE300-0315-4
2×150/2×185
150/185
2×150/2×185
2×150/2×185
M12
31–40
IPE300-0355-4
2×185/3×150
185/2×120
2×185/3×150
2×185/3×150
M12
31–40
IPE300-0400-4
3×150/3×185
2×120/2×150
3×150/3×185
3×150/3×185
M12
31–40
IPE300-0450-4
3×185/3×185
2×150/2×150
3×185/3×185
3×185/3×185
M12
31–40
IPE300-0500-4
3×185
2×150
3×185
3×185
M12
31–40
Note:
1. Cables of the sizes recommended for the main circuit can be used in scenarios where the
ambient temperature is lower than 40°C, the wiring distance is shorter than 100 m, and the
current is the rated current.
2. The terminals P1, (+), PB, and (-) are used to connect to DC reactors and braking accessories.