IPE300 series engineering VFD Optional peripheral accessories
-354-
3. The values on the left and right sides of "/" indicate the recommended cables for heavy and light
loads respectively.
Table D-2 AC 3PH 520V(-15%)690V(+10%)
VFD model
Recommended cable size (mm
2
)
Terminal
screw
Fastening
torque (Nm)
RST
UVW
P1
(+)
PB
(+), (-)
PE
IPE300-0022-6
4/6
4/6
4/6
4/6
M8
911
IPE300-0030-6
6/10
6/10
6/10
6/10
M8
911
IPE300-0037-6
10/10
10/10
10/10
10/10
M8
911
IPE300-0045-6
10/16
10/16
10/16
10/16
M8
911
IPE300-0055-6
16/25
16/25
16/25
16/25
M10
1823
IPE300-0075-6
25/25
25/25
25/25
25/25
M10
1823
IPE300-0090-6
25/35
16/16
25/35
25/35
M10
1823
IPE300-0110-6
35/50
16/25
35/50
35/50
M10
1823
IPE300-0132-6
50/-
25/-
50/-
50/-
M10
1823
IPE300-0160-6
70/95
35/50
70/95
70/95
Nuts are used for
terminals. You are
recommended to
use a wrench or
sleeve.
IPE300-0185-6
70/95
35/50
70/95
70/95
IPE300-0200-6
95/95
50/50
95/95
95/95
IPE300-0220-6
95/-
50/-
95/-
95/-
IPE300-0250-6
95/150
50/70
95/150
95/150
IPE300-0280-6
150/185
70/95
150/185
150/185
IPE300-0315-6
185/-
95/-
185/-
185/-
IPE300-0355-6
185/-
95/-
185/-
185/-
IPE300-0400-6
95/2×95
95/95
95/2×95
95/2×95
IPE300-0450-6
95/2×150
95/150
95/2×150
95/2×150
IPE300-0500-6
150/2×150
150/150
150/2×150
150/2×150
IPE300-0560-6
150/2×185
150/185
150/2×185
150/2×185
IPE300-0022-6
4/6
4/6
4/6
4/6
Note:
1. Cables of the sizes recommended for the main circuit can be used in scenarios where the
ambient temperature is lower than 40°C, the wiring distance is shorter than 100 m, and the
current is the rated current.
2. The terminals P1, (+), PB, and (-) are used to connect to DC reactors and braking accessories.