EasyManua.ls Logo

INVT IPE300 Series - P93 Group-PT100 PT1000 Temperature Protection Functions

INVT IPE300 Series
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IPE300 series engineering VFD Function parameter list
-241-
P93 group––PT100/PT1000 temperature protection functions
Function
code
Name
Description
Default
Modify
P93.00
PT100/PT1000
temperature
detection
enabling
0x000x11
Ones place: PT100 temperature detection
0: Disable
1: Enable
Tens place: PT1000 temperature detection
0: Disable
1: Enable
0x00
P93.01
PT100
overtemperature
protection point
0.0150.0°C
100.0°C
P93.02
PT100
overtemperature
pre-alarm point
0.0150.0°C
85.0°C
P93.03
Upper limit of
PT100
calibration
temperature
50.0150.0°C
150.0°C
P93.04
Lower limit of
PT100
calibration
temperature
-20.050.0°C
-20.0°C
P93.05
Upper limit of
PT100
calibration digital
quantity
04096
3800
P93.06
Lower limit of
PT100
calibration digital
quantity
04096
0
P93.07
PT1000
overtemperature
protection point
0.0150.0°C
100.0°C
P93.08
PT1000
overtemperature
pre-alarm point
0.0150.0°C
85.0°C
P93.09
Upper limit of
PT1000
calibration
temperature
50.0150.0°C
150.0°C