IPE300 series engineering VFD Basic operation guidelines
-78-
Function
code
Name
Description
Default
2: Input set through encoder, used
together with HDIA
P05.45
HDIB lower limit frequency
0.000 kHz P05.47
0.000kHz
P05.46
Corresponding setting of
HDIB lower limit frequency
-300.0%300.0%
0.0%
P05.47
HDIB upper limit frequency
P05.4550.000kHz
50.000kHz
P05.48
Corresponding setting of
HDIB upper limit frequency
-300.0%300.0%
100.0%
P05.49
HDIB frequency input filter
time
0.000s10.000s
0.030s
P05.50
AI1 input signal type
01
0: Voltage
1: Current
0
5.5.10 Analog output
The VFD carries one analog output terminal (010V/020mA) and one high-speed pulse output
terminal. Analog output signals can be filtered separately, and the proportional relation can be
adjusted by setting the max. value, min. value, and the percentage of their corresponding output.
Analog output signal can output motor speed, output frequency, output current, motor torque and
motor power at a certain proportion.
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.16
AO1
HDO
P06.17
P06.18
P06.19
P06.20
P06.27
P06.28
P06.29
P06.30
P06.21
P06.31
(Default value is 0)
(Default value is 0)
P06.00
(HDO output type)
0
1
P06.00
0: Open collector high-speed
pulse output
1: Open-collector output
Analog output curve setting
Analog output selection Analog output filter
Terminal output is described as follows:
Setting
Function
Description
0
Running frequency
0Max. output frequency