Address format RD/WR Unit Note Adjustment range Default
45 USHORT RD/WR mA Response threshold of 0 .. 200 5
current measuring I1 .. I3
50 SHORT RD/WR - Password 0 .. 999 0 (No password)
100 SHORT RD/WR - Measured value address,
Digital output 1 0..32000 874
101 SHORT RD/WR - Measured value address,
Digital output 2 0..32000 882
102 FLOAT RD/WR Wh Pulse value,
Digital output 1 -1000000..+1000000 1000
104 FLOAT RD/WR Wh Pulse value,
Digital output 2 -1000000..+1000000 1000
106 SHORT RD/WR 10ms Min. pulse length (1=10ms)
Digital output 1/2 1..1000 5 (=50ms)
206 SHORT RD/WR s “Drag indicator” period duration 300..3600 900
207 SHORT RD/WR s “Drag indicator” capture time 1..20 10
208 SHORT RD/WR - Config. Digital input 1 0 .. 2 0
0= internal synchronisation
1= external synchronisation (NO)
2= external synchronisation (NC)
500 SHORT RD/WR - Connector pin assignment, I L1 -3..0..+3
1)
+1
501 SHORT RD/WR - Connector pin assignment, I L2 -3..0..+3
1)
+2
502 SHORT RD/WR - Connector pin assignment, I L3 -3..0..+3
1)
+3
503 SHORT RD/WR - Connector pin assignment, U L1 0..3
1)
1
504 SHORT RD/WR - Connector pin assignment, U L2 0..3
1)
2
505 SHORT RD/WR - Connector pin assignment, U L3 0..3
1)
3
506 SHORT RD/WR - Min- und Reset max. values 0..1 0
507 SHORT RD/WR - Reset energy meter 0..1 0
508 SHORT RD/WR - force EEPROM descr. 0..1 0
Note: Energy values and min-max values are recorded into the EEPROM every 5 minutes.
1)
0 = No measurement of the current or voltage path.
2)
The setting 8 is equal setting 0.