19
UMG 96RM-E
c
Caution!
Voltages which exceed the per-
mitted networkrated voltage
must be connected via a voltage
transformer.
c
Caution!
The UMG 96RM-E is not suitable for
measuring DC voltages.
c
Caution!
The voltage measurement inputs
on the UMG 96RM-E are dangerous
if touched!
When connecting the voltage to be measured,
the following must be observed:
Isolation device
A suitable circuit breaker must be fitted to disconnect
and de-energise the UMG 96RM-E.
The circuit breaker must be placed in the vicinity of
the UMG 96RM-E, be marked for the user and easily
accessible.
The circuit breaker must be UL/IEC certified.
Overcurrent protection device
An overcurrent protection device must be used for
line protection.
For line protection, we recommend an overcurrent
protection device as per the technical specifications.
The overcurrent protection device must be suitable
for the line cross section used.
The overcurrent protection device must be UL/IEC
certified.
A circuit breaker can be used as an isolating and line
protection device. The circuit breaker must be UL/IEC
certified.
Measured voltages and measured currents must
derive from the same network.