3 Operating Conditions
34 Jetter AG
Operating Parameters
EMI - Immunity to Interference
Power Interfaces
Parameter(s) Value(s) Ref. standard
Burst (fast transients) Test voltage 2 kV
Repetition frequency 5 kHz
Capacitive interference
Criterion B
(Electromagnetic environment in
industrial plants)
DIN EN 61800-3
DIN EN 61000-4-4
Operating Parameters
EMI - Immunity to Interference
Signal interfaces
Parameter(s) Value(s) Ref. standard
Burst (fast transients) Test voltage 1 kV
Repetition frequency 5 kHz
Capacitive interference
Criterion B
(Electromag. envir. in ind. plants)
DIN EN 61800-3
DIN EN 61000-4-4
Guided radio
disturbances
Frequency 0.15 ... 80 MHz
Test voltage 10 V
AM 80 % at 1 kHz
Criterion A
(Electromag. envir. in ind. plants)
DIN EN 61800-3
DIN EN 61000-4-6
Operating Parameters
EMI - Immunity to Interference
Process-Related Measuring and Control Lines
Parameter(s) Value(s) Ref. standard
Burst (fast transients) Test voltage 2 kV
Repetition frequency 5 kHz
Capacitive interference
Criterion B
(Electromag. envir. in ind. plants)
DIN EN 61800-3
DIN EN 61000-4-4
Impulse voltages tr/th 1.2/50 µs, 8/20 µs
1 kV (phase to ground)
Criterion B
(Electromag. envir. in ind. plants)
DIN EN 61800-3
DIN EN 61000-4-5
Guided radio
disturbances
Frequency 0.15 ... 80 MHz
Test voltage 10 V
AM 80 % at 1 kHz
Criterion A
(Electromag. envir. in ind. plants)
DIN EN 61800-3
DIN EN 61000-4-6