JetMove D203
Jetter AG 29
3 Operating Conditions
DANGER
Danger in the event that the operating parameters for the
"Safe Torque Off" option of the JM-D203-...-S1 amplifiers
are not complied with.
Dangerous injuries can occur!
For example from
electric shock because the electrical safety has been violated by not complying
with the degree of pollution;
crushing if the functionality of the safety function STO is no longer guaranteed.
Make sure that the following operating parameters are met.
Operating Parameters
Power Rating
Parameter(s) Value(s) Reference
standard
Power rating Switching device at X1:
1 * AC 230 V, 50 / 60 Hz <= 10 A
(AC 195 ... 265 V)
Logic unit via X10:
DC 24 V, SELV / PELV <= 1.3 A
(DC 20 ... 28.8 V)
Option: -JC24X:
Logic unit via X10:
additionally DC 24 V <= 0.35 A
LCD via X10:
additionally DC 24 V <= 0.75 A
Digital outputs via X30:
DC 24 V, SELV / PELV <= 6 A
(DC 20 ... 28.8 V)
Option: -S1
For each channel via X73 / X83:
DC 24 V, SELV / PELV <= 50 mA
(DC 20 ... 30 V)
Variations of the
mains power supply
Speed of changing the frequency:
2 %/s max.
Voltage imbalance:
2 % max.
Voltage dips at rated output and
rated voltage: 10 ms max.