12 Option -JC24X
96 Jetter AG
12.3 Digital Inputs
12.3.1 Technical data
Technical Data - Digital Inputs
16 digital inputs DC 24 V -15 % ... +20 %
Type PNP
Input terminals Plug-in terminal blocks
LEDs, inputs 1-16 24 volt are applied to the input.
The LEDs are only lit, if the JM-D203
-JC24X is connected to the voltage supply.
Heat loss of logic circuit 0.3 Watts
Rated input voltage DC 24 V -15 % ... +20 %
Voltage range 0 ... 30 V
Input current typically Approx. 7.5 mA
Input resistance 3.0 kΩ
Input delay time approx. 3 ms (from 0 to 1, and from 1 to 0)
Signal voltage ON 17 V min.
Signal voltage OFF 5 V max.
Signal processing Dynamic
Electrical isolation Electrical isolation to logic is available
INFO
All digital inputs and outputs have got the same reference potential.
A digital output may directly (without additional load) be connected to a digital
input.