JetMove D203 7.1 Mains Power Supply
Jetter AG 49
7 Description of Connections
For axis A, the connection designations X71 through X74 are available.
For axis B, the connection designations X81 through X84 are available.
7.1 Mains Power Supply
Specification of terminal X1
3-pin screw clamping terminal (type PC 4/ 3-ST-7.62)
Cross-sectional area of the connecting cable: 0.25 - 4.0 mm
2
(AWG 24 - AWG 12)
Bladed screw-driver: 0.6 x 3.5 x 100 mm
Stud torque for the screw clamping terminal:
0.5 Nm - 0.6 Nm (4.4 - 5.3 lbf-inch)
Connecting cable specifications
Cable size: 3 * 1.5 mm² (AWG 16(3))
Material: Copper
Temperature class: 60 °C
Stripping length of cores: 6 mm
Bootlace ferrules are recommended
Cable shielding
Not needed
Fig. 8: Connection of the mains power supply
Power Supply
1-Phase Connection
Terminals X1 Signal Specifications
L L AC 230 V between
mains phase and
neutral
NN
PE PE conductor
yellow / green
PE
X1
L PEN
blue
Neutral
black
Mains Phase
Fuse or
Overcurrent Circuit Breaker or
Motor Current Circuit Breaker