JetMove D203 5.1 Electrical Specification
Jetter AG 37
5 Technical Data
5.1 Electrical Specification
DANGER
Danger in the event that the Electrical Specification for the
"Safe Torque Off (STO)" option of the JM-2xx-xxx...-S1 amplifiers
is not complied with.
Serious injuries can occur!
For example from
electric shock because the electrical safety has been violated by not observing
the degree of pollution;
crushing if the functionality of the safety function STO is not ensured.
Make sure that the following electrical specifications are met.
Electrical Specification
Rated voltage supply Direct suuply U
eff
= 230 V
Common mode of the voltage 2 % max.
Voltage dips 10 ms max. at rated power
and rated voltage
48 ... 62 Hz
Frequency change 2 % / s max.
Type of power supply connection one-phase: direct (U
eff
= 230 V: L to N)
Power supply tolerance U
eff
= 195 V ... 265 V(-15 % ... + 15 %)
Inrush current limitation < 7 A limited to typ. 350 ms during the
switch-on-sequence
Refer to “Time between deactivating and
activating the mains power supply" on
page 41