5 Technical Data
38 Jetter AG
Overload Protection An external overload protection is required.
There are three options:
– Circuit-breaker 10 A C
– Fuse 10 A M (medium time lag)
– Motor circuit breaker 10 A
For systems with NRTL approval use
overload protection devices that are NRTL
listed (acc. To UL 508)(NKJH) ) self
protected combination motor controller
(specification: 10 A).
The JetMove D203 is suitable for use on a
circuit capable of delivering not more than
5000 (rms) symmetrical Amperes, 230 Volts
maximum.
Supply cable
Cable size
Material
Temperature class
3 * 1.5 mm
2
min. (AWG 16)
Copper
> 60 °C
Maximum output voltage of the
motor
450 V
Motor output current at an ambient
temperature of 45 °C
Nominal current: I
eff
= 3 A per axis
Peak current for 30 seconds: I
eff
= 6 A per
axis (the time depends on the heat sink
temperature)
See “INFO 1” on page 41.
Continuous output 0.5 kW per axis
Short-circuit protection, motor side Designed for
• phase to phase
• phase to earth
Motor overload protection See “Motor Protection” on page 43.
Motor cable
Cable size
Material
Capacitance
Temperature class
Maximum length
4 * min. 0,75 mm
2
min. (AWG 18)
Copper
< 150 pF/m
> 60 °C
50 m max.
(for greater length please contact Jetter AG)
Electrical Specification