7 Description of Connections
54 Jetter AG
For connection with motor holding brake
Dimensions of the motor mating connector are specified in millimeters.
Motor Power Cable - Cable Confection # 24.1
Wiring Terminals
JetMove D203
Shield Mating
Connector of the
Motor (female,
solder side)
4 x 1.5 mm
2
(2 x 1.5 mm
2)
(AWG 16(6))
Highly flexible
6-wire cable with
PE (GND)
(cable
with separate
shield for brake
wires and overall
shield)
The wires are
equipped with wire
end ferrules.
Connect both sides of the shield
with the greatest possible surface
area!
Use metallized housing only!
Pin Wire Number Signal Pin
X74 / X84.U2 1 Phase 1 1
X74 / X84.V2 2 Phase 2 5
X74 / X84.W2 3 Phase 3 2
X74 / X84.PE Yellow-green PE conductor
X72 / X82.BRAKE+ 5 Brake + 6
X72 / X82.BRAKE- 4 Brake - 4
Cores
Shield Case
360° round
connection of
the shield mesh
Seal and
pull relief
element
Union nut
Adapter
Cable
Mating
Connector
Solder Side
Solder Side
18
26
65
5
24
6
1
JetMove D203
Cable Strap
Motor Cable
1
m
m
m
a
x
.
1
5
m
m
Mating
Connector

Table of Contents

Related product manuals