Table 7: Analog input ranges
English range Metric range
Analog input
Low High Units Low High Units
Leaving Chilled Liquid Temperature 0.0 82.0 °F -17.7 27.7 °C
Return Chilled Liquid Temperature 0.0 94.1 °F -17.7 34.5 °C
Leaving Condenser Liquid Temperature 8.0 133.5 °F -13.3 56.3 °C
Return Condenser Liquid Temperature 8.0 133.5 °F -13.3 56.3 °C
Evaporator Refrigerant Temperature (Optional) 0.0 126.1 °F -17.7 52.3 °C
Discharge Temperature 31.8 226.3 °F -0.1 107.9 °C
Condenser Pressure 0.0 300.0 PSIG 0.0 2069 KPAG
Condenser Temperature
1
-98.7 160.1 °F -72.6 71.7 °C
Evaporator Pressure 0.0 125.0 PSIG 0 862 KPAG
Evaporator Temperature
1
-44.9 64.7 °F -42.7 18.1 °C
Refrigerant Level 0.0 100.0 % 0.0 100.0 %
Drop Leg Refrigerant Temperature 0.0 121.7 °F -17.7 49.8 °C
Motor Housing Temperature 31.8 226.3 °F -0.1 107.9 °C
1 Saturation temperatures are calculated values. They will display XXX if the pressure used for the calculation is out of
range.
31
YMC
2
Mod B with OptiView
Control Center

Table of Contents

Other manuals for Johnson Controls YORK YMC2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK YMC2 and is the answer not in the manual?

Johnson Controls YORK YMC2 Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK YMC2
CategoryChiller
LanguageEnglish

Related product manuals