Ensure that the cool air supply you provide through the cabinet can adequately dissipate
the thermal output of the services gateway.
Install the services gateway as close as possible to the front of the cabinet so that the
cable management system clears the inside of the front door. Installing the chassis
close to the front of the cabinet maximizes the clearance in the rear of the cabinet for
critical airflow.
Route and dress all cables to minimize the blockage of airflow to and from the chassis.
Related
Documentation
SRX320 Services Gateway Cabinet Size and Clearance Requirements on page 31