117
Technical Data
7.6 Hardware outputs
Relay
outputs
Switching
stages
5 on basic device, one of these can be congured as fan
Switching
capacity
250V (AC) / 2A per relay
Alarm relay Apparent
power
250V (AC) / 2A oating, congurable as fans or switching
stage
Interface Serial inter-
face
RS-485
Bus protocol KBR Energy bus / Modbus
Transmission
speed
38.400 baud, can be selected on Modbus 4,800, 9,600,
19,200baud
Address
assignment
Can be addressed up to address number 9999 for KBR
eBus; scan mode can be activated on the device
Bus addresses for Modbus 1 to 247 congurable on the
device
Display and
conuration
interface
Serial inter-
face
RS-485 (RJ12)
Module bus
interface
Serial inter-
face
RS 485 (RJ12) for ready-made KBR system cable (6-pin
modular cable, unshielded), max. length 30m if placed
suitably

Table of Contents

Related product manuals