Commissioning
3.1 Controller not congured
If a controller which has not been congured is to be started up, the following procedure
has to be performed step by step.
1. Conguration additional modules (multisio D2-1TI2RO,
multisio D2-4RO, multisio D4-4RO ISO, multisio D2-4CI and multimess D4)
If there are no additional temperature, relay or induced current measuring modules, this
step can be skipped. To congure additional modules, connect them and the supplied
bus line to the basic module. The additional modules can then be activated individually
using a scan mode, which has to be triggered via the basic module's operating panel
and the DIP switches or scan buttons on the additional module. If the compensation unit
consists of several cabinets, the correct cabinet assignment has to be set up.
Detailed instructions for this step are given in chapter Settings under Modules / Display
submenu.
2. Conguring current transformer values
All current transformer parameters need to be congured correctly for the compensation
controller to function properly. Primary and secondary current of the transformer have
to be set. These parameters can be found on the nameplate of the current transformer. In
addition, the phase allocation of the transformer needs to be congured correctly. In the
controller, the phase (L1, L2, L3) in which the current transformer is integrated has to be
set.
You can nd more detailed information on this topic in chapter Start-up under Transform-
er settings submenu.
3. Setting target cosine
You can ask your electricity supplier for the target cos, which should be set up at this
point. By default, the target cos is set to 0.95 inductive (see the "Default settings" chap-
ter).
You can nd more detailed information on this topic in chapter Start-up under Target
cosine submenu.
NOTE
Summer-CosPhi:
For a specied, adjustable time range, the target cosine can be altered, deviating from
the default settings (Menu item DST, Summer-target cosine). The setting range for the
time range goes from month 01 to month 12. beginning or ending with the 1st day of the