5.13.8.2 Submenu System
The System submenu contains the following items:
1. Parameters
2. Reset
For the item Parameters, the switching behavior,
temperature parameters and limits can be adjusted.
The switching behavior comprises the following options:
Switch-on and switch-o hysteresis Input in % with respect to the stage power
of the smallest available capacitor stage
Switching
times:
Idle time after
compensation
Input in seconds (0–300 sec.)
Alarm delay
for FTS
Input in seconds (3–3000 sec.) until the
message Facility Too Small is issued, i.e.
the alarm cosφ was not reached after
expiry of the time set.
Switching interval Input in seconds
(0 to 10 sec.). It is specied here at what
interval the capacitor stages must be
hooked up if there is insucient compen-
sation power, to achieve the set target
cosφ.
Attenuation coecients The attenuation coecients (0 to 6) are
there to reduce the display uctuations;
the measuring cycle of the controller is
not inuenced.
System operation