System operation
5.13.6 Q-Control:
The following modes can be selected:
DI 3 Q/P rated (change by digital input)
AI 3 Q/P rated (change by analog input)
U 3 Q/P rated (change by voltage curve)
P 3 Q/P rated (change by active power curve)
o The function is deactivated, i.e. the device is working with the
value programmed as target cosine1
Parameters:
Q parameters
Q-Control Yes/No
P rated 100.0 kW
Target Q
Q/Pn1 power consumption 0.75 capacitive to 0.75 inductive
Q/Pn2 energy recovery 0.75 capacitive to 0.75 inductive
Q/Pn3 Alarm 0.00 to 1.73 inductive
Mode DI 3 Q
t-delay 000 Seconds
Q/Pn A 0.50 ind.
Q/Pn B 0.33 ind.
Q/Pn C 0.33 cap.
Q/Pn D 0.50 cap.
Mode AI 3 Q
t-delay 000 Seconds
Q/Pn A 0.90 ind.
Q/Pn B 1
% A 0%
% B 100%
AI 4–20 mA YES