Appendix - multisio D2 4CI
8.5.6 Electrical connection
Connection
elements
Plug-in terminals
Permissible
cross-section
of the connecting
cables
2.5 mm
2
Measuring voltage
inputs
Fuse max. 6 A
Measurement
current inputs
Fuse NONE!!! Always short-circuit current
transformer terminals k and l before
opening the circuit!
Input
control voltage
via measuring voltage
Module bus
connection
Connection material Ready-made KBR system cable (6 pole
modular cable,
unshielded), max. length 30m when
suitably placed
8.5.7 Mechanical data
Top-hat rail
devices
Housing dimensions 90 x 71 x 61 mm (H x W x D)
Mounting type Wall mounting on DIN rail 7.5mm deep,
in accordance with DIN EN 50022
Suitable for distribution board mount-
ing
Weight Approx. 175g