5.3 Setting range of the congurable parameters:
primary voltage 1V to 9999kV Ph-Ph
Secondary voltage 100 V to 500 V Ph-Ph
Primary current 1 A to 99.99 kA
Secondary current 1 and 5 A
Rot.eld U L1N, L2N, L3N, L12, L23, L31
Rot.eld I L1, L2, L3, -L1, -L2, -L3
Consumption target cosφ ind. 0.80 to cap. 0.80
Recovery target cosφ ind. 0.80 to cap. 0.80
FTS alarm cosφ ind. 0.50 to cap. 0.50
Attenuation coecient for current 0 to 6
Attenuation coecient for voltage 0 to 6
Attenuation coecient Q
miss
0 to 6
Idle time 0 to 300 sec.
Alarm relay time 0 to 3000 sec.
Hysteresis connection 70 to 150%
Hysteresis switch-o 70 to 150%
Switching interval 0 to 480 sec.
Operating cycle limit 0 to 99990
Cabinet No. 1 to 6
Stage power 0 to 999.9 kvar inductive or capacitive
Discharge time 0 to 900 sec.
Detuning 0, 5.5, 7, 8, 12.5, 14%
Stage switching mode Automatic, manual o, manual on
Harmonics monitoring 0 to 99%, deactivatable
Overvoltage switch-o Dependent on primary voltage
Excess current switch-o 110% to 200%
Undercurrent switch-o 0 to 90%
Limit THD 0 to 10%
Switching threshold fan 0 to 70°C / hysteresis = 0°C to 25°C
Operating point alarm 0 to 70°C / hysteresis = 0°C to 25°C
Operating point overtemperature 0 to 70°C / hysteresis = 0°C to 25°C
Scanning frequency Automatic, xed 50Hz, xed 60Hz
Password No password (9999, meaning all functions
are accessible)
Language display German, English, French
Contrast setting 60% to 100%