V7.00
24905_EDEBDA0272-5019-1_EN
17
Commissioning
3 Commissioning guideline
for the multicomp D6-xxx-7
This guideline helps you to correctly start up the compensation controller
multicomp D6-xxx-7 . It provides you with step by step instructions to help you nd
the options relevant for you in the operating instructions.
To begin with, there are two cases in which the commissioning procedure for the
multicomp D6-xxx-7 diers.
Case 1: You have bought a complete compensation unit from KBR, and the controller
is already installed. If this is the case, certain settings are already precongured in the
controller.
Case 2: You only bought the controller, or the controller with additional modules
(multisio D2-1T2RO, multisio D2-4RO, multisio D4-4RO ISO, multisio D2-4CI and
multimess D4) and individual capacitor stages, but the device is not assembled. In this
case, the controller is delivered with the default settings (refer to chapter Default settings)
and has thus not been precongured.
IMPORTANT SAFETY INFORMATION
CAUTION
The discharge times are automatically predened for the following programmed stage
powers. However, these must be checked and corrected if they dier from the capacitor
specications.
Capacitor power Discharge resistance Discharge time
2.5 kvar – 7.5 kvar 300 kOhm 60 seconds
10 kvar–17.5 kvar 300 kOhm 120 seconds
20 kvar and above 300 kOhm 180 seconds