Technical Data
7.8 Mechanical data
DIN rail measur-
ing device
Housing dimensions 90x106 x61mm (H x W x D),
Mounting type Wall mounting on DIN rail
7.5 mm deep, in accordance with DIN
EN 50022
Weight Approx. 650g
Dimensioned drawing
7.9 Ambient conditions / electrical safety
Surrounding
conditions
Standards DIN EN 60721-3-3/A2: 1997-07;
3K5+3Z11; (IEC721-3-3; 3K5+3Z11)
Operating temperature K55 (-5°C …. +55 °C)
Air humidity 5 % … 95 %, non-condensing
Storage temperature K55 (-25°C …. +70°C)
Operating height 0…2,000m above sea level
Electrical
safety
Standards
DIN EN 61010-1: 2011-07
Protection class I
Overvoltage category CATIII
Rated insulation voltage 4kV
Protection type Standards IP20 in accordance with DIN EN 60529:
2014-09
EMC Standards DIN EN 61000-6-2:2006-03 +
amendment 1:2011-03
DIN EN 61000-6-3:2011-09 +
amendment 1:2012-11
DIN EN 61326-1:2013-07