12. By pressing the scan sensor button for approx. 4 seconds, set the measuring module
into scan mode (the green status LED ashes more quickly).
The multicomp basic module recognizes the measuring module and adds it to the list of
connected modules. You can now scan further modules, which are automatically added
to the module list or, by touching the stop button, end the scanning process. The multi-
comp D6-xxx-7 can manage a maximum of six modules.
8.9.10 Connections
Terminals 10–13
(L1, L2, L3, N)
Measuring voltage. The power supply
of the device is also provided by the
measuring voltage. For technical
data, please refer to the nameplate.
Terminal
20 (k1) and 21 (l1)
22 (k2) and 23 (l2)
24 (k3) and 25 (l3)
Measuring inputs for current. The
measuring inputs for current must be
connected via current transformers
x/1A AC or x/5A AC. When connecting
transformers, pay attention to the
energy ow direction and the correct
assignment of measuring voltage
inputs to the current transformers.