Commissioning
3.2 Default settings after reset
Primary voltage/secondary voltage 400V/400V Ph-Ph
Primary current/secondary current 1000 A/5 A
Cosφ 1 (target cosφ) inductive 0.95
Cosφ 2 (target cosφ with energy recovery) inductive 1.00
Cosφ 3 (alarm cosφ for FTS message) inductive 0.92
Damping coecient for current and
voltage
2
Temperature measurement Active
Switching threshold fan 28°C, hysteresis 5°C
Operating point alarm 45°C, hysteresis 5°C
Operating point emergency o 48°C, hysteresis 5°C
Idle time 30 sec.
Alarm relay time 1200 sec.
Alarm relay NC contact
Hysteresis connection 70% of smallest available stage
Hysteresis switch-o 100% of smallest available stage
Switch attenuation (stage interval) 8 sec.
Operating cycle limit 80,000
Stage power No stage power programmed
Stages System type standard
Discharge time 180 sec.
Detuning 7 %
Cabinet No. 1
Stage 5 as fan
Continued on the right