Appendix - multisio D2 4RO accordance with ISO
8.3.4 DIP switch functions
8.3.4.1 Operating mode
For every output, the multisio 1D4-4RO ISO dierentiates between the
operating modes normal” and manual. Switching is performed via the
DIP switches 5 to 8.
The DIP switches are assigned to the outputs as follows:
• DIP switch 5 determines the operating mode of output1
• DIP switch 6 determines the operating mode of output2
• DIP switch 7 determines the operating mode of output3
• DIP switch 8 determines the operating mode of output4
If the DIP switch is set to O, the respective output is in the normal operating mode. If the
DIP switch is set to On, the respective output is in the manual operating mode.
Illustrated switch setting:
OFF = white
ON = grey
8.3.4.2 DIP switch settings
Normal operating mode
In the normal operating mode, the state created in the module is issued at the corre-
sponding output.
Manual operating mode
In manual operating mode, the state of DIP switches 1 to 4 is issued at the corresponding
output instead of the state created by the module.
The DIP switches are assigned to the outputs as follows:
DIP switch 1 determines the state of output 1
DIP switch 2 determines the state of output 2
DIP switch 3 determines the state of output 3
DIP switch 4 determines the state of output 4
If the DIP switch is set to O, the output is passive / o. If the DIP switch is set to On, the
output is active / on