V7.00
24905_EDEBDA0272-5019-1_EN
134
8.5.3 Device memory
Main and data memory 16kB RAM unbuered
Program / parameter memory 256 kB Flash / 4kB EEP
Energy meter P+, P-, Q+, Q- saved in EEP
Limit violation Recording time 8 min. for average current
value, saved in RAM
8.5.4 Power supply
Measuring module power supply 50...230...280 VAC Ph-N, 3.2VA, 50/60Hz
from the measuring voltage
Module bus power supply ext. 24VDC, 0.3W,
via RJ12 module bus connector
8.5.5 Hardware inputs and outputs
8.5.5.1 Inputs
Voltage
measuring inputs
U
L1-N
; U
L2-N
; U
L3-N
3 x 50 V...230 V...280 V AC 50/60 Hz
Input impedance 900 kOhm each (Ph-N)
Current
measuring inputs
I
L1
; I
L2
; I
L3
3 x 0,02A...5A...6A AC
Power consumption <_ 0.3 VA per input at 6A
8.5.5.1 Outputs
serial
interface
Module bus RS485 via RJ12 interface
Baud rate 38400
Address assignment Can be addressed using the display or
visual energy (connection via multisio
3D2 ESBS gateway)
multisio D2 4CI - Appendix